Product Catalogue

Temperature Controller KT-101L
Home >> Prodcut Catalogue >> Controller for Refrigeration
| Temperature Controller KT-101L | |
| Brand Name: | Neutral or KingTill |
| Brief Info: | Compressor: N.O. 30A/250VAC, Sensor: NTC, one sensor, 2m(L) |
|
|
|
Product Description
Temperature Controller KT-101L
Function:
Temperature Display and Control / Automatic defrost after turning off compressor
High and Low temperature alarm / Value Storing / Self Testing /Parameter Locking
Technical Parameter:
1. Power Supply: 12VAC output transformer
2. Temperature sensor: NTC, one sensor, 2m(L)
3. Temperature Measuring range: -45~99℃ Accuracy:±1℃
4. Temperature Controlling range: -40~40℃ Default :0℃
5. Dimension: 142(L) × 38(W) × 35(D) mm
Mounting Size: 137(L) × 31.5 (W) mm
6. Operating environment: Temp.:-10~60℃; Relative Humidity: 20%~90%(No condensing)
7. Relay output contact capacity
Compressor: N.O. 30A/250VAC
Menu:
| Parameter | Function | Set range | Default |
| E1 | Lower set-point limit | -40℃~Set temp. | -30℃ |
| E2 | Higher set-point limit | Set temp.~40℃ | 30℃ |
| E3 | Temp.Return Difference | 1~20℃ | 5℃ |
| E4 | Comp.start delay time | 0~10Min | 2Min |
| E5 | Room Temp. calibration | -20~20℃ | 0 |
| F1 | Defrost Time | 1~90Min | 20Min |
| F2 | Defrost Cycle | 0~24Hr | 6Hr |
| F4 | Display during defrost |
0=Nomal display 1=Last value before defrost |
0 |
| C2 | High temperature alarm | Set value~49℃~OFF | 40℃ |
| C3 | Low temperature alarm | OFF~-44℃~Set value | OFF |
| C4 | Alarm delay time | 1~90Min | 30Min |